SEL-2100 High-Speed Logic Processor

SEL-2100 High-Speed Logic ProcessorConnect up to 15 SEL-2505 Remote I/O Modules to one SEL-2100 Logic Processor. Each module provides eight digital inputs and eight digital outputs. Use SELOGIC® control equations in the SEL-2100 to define the logic that executes in the SEL-2100. Use remote digital inputs to calculate the values for the digital outputs. The SEL-2100's internal logic process is fast and deterministic. This means that all logic is processed in 4 ms.

Features
  • Extended Temperature Range
  • EMI/RFI and ESD Tested
  • Deterministic Processing Time
  • Rack Mount
  • Sequential Events Recorder
  • Worldwide, Ten-Year Warranty
Technical Specifications
Communications Ports 1 front / 16 rear, DB-9 RS-232
Data Rates 300-38400 bps
Power Supply
125/250 Vdc or Vac 85-350 Vdc or 85-264 Vac
48/125 Vdc or 125 Vac 38-200 Vdc or 85-140 Vac
24/48 Vdc 18-60 Vdc
Real Time Clock
Accuracy  ±1 min./yr @ 25°C
±5 ms with IRIG-B input
Protocols
SEL MIRRORED BITS High-speed control. (Up to 15 ports)
DNP3 Level 2 1 port
Environmental
Operating temperature -40° to +85°C
Humidity 95% Noncondensing
Weight 8 lb (3.5 kg)

 

Sense contacts at one location and send them to multiple locations with the SEL-2100

Application

  • Sense contacts at one location, and send them to multiple locations. For example, sense level limit switches on the main tank with one SEL-2505, which sends the information to the
    SEL-2100. In turn, the SEL-2100 sends the limit-switch states to each of seven SEL-2505 modules that are mounted with controllers for parallel processes that send liquid into the main tank.
  • Build high-speed interlocking and remedial action schemes to prevent damage or improve process availability. Sense pressure limit switches and rupture discs on a chlorine tank. If a problem is detected, activate evacuation procedures, and send information to SEL-2505 modules located in the control cabinets, to adjust or stop processes to close valves and stop mixing processes.
SELOGIC Control Equations and Equation Operators
SELOGIC control equations include: latches, relay output control, timers, transmit controls, and logic variables.

SELOGIC equation operators include; Rising edge detect, falling edge detect, AND, OR, NOT, and parentheses.

 

For shipping outside the USA, or for tax exempt orders, please contact SEL Customer Service to place your order.

Ordering Options
Description Part Number Price

20-60 Vdc power supply; no I/O

2100xx2xxH

$2,100

Add to Order

38-200 Vdc / 85-264 Vac power supply; no I/O

2100xx3xxH

$2,100

Add to Order

20-60 Vdc power supply with 16 48-Vdc inputs and four output relays

2100xx242H

$2,730

Add to Order

38-200 Vdc / 85-264 Vac power supply with 16 125-Vdc inputs and four output relays

2100xx344H